GDKC-15 Series Circuit Breaker Analyzer
I-high-voltage circuit breaker yenye yezona zixhobo zokulawula ezibalulekileyo kwinkqubo yamandla.I-GDKC-15 Series isetyenziselwa ukuvavanya iimpawu eziguqukayo ze-high voltage breaker circuit.Kulula ukusebenza, ngokuchaneka okuphezulu.
| GDKC-15A | I-GDKC-15B | I-GDKC-15C | I-GDKC-15D | GI-DKC-15E | I-GDKC-15F | I-GDKC-15G | I-GDKC-15H | |
| Uqhagamshelwano lwentsimbi | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 |
| Ukuvala ukuchasana | 6 | 6 | 6 | 6 | 6 | 6 | 6 | |
| Uqhagamshelwano lwegraphite | 3 | 3 | 3 | 3 | 6 | |||
| Ukumisa okuphindwe kabini | 3 | 3 | 3 | 6 | ||||
| Uxhathiso olunamandla (Isixhasi sangaphambi kokufakwa) | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
| Ukuxhathisa okuzinzileyo | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
| Ukuchasa umhlaba | 3 | 6 |
●Ilungele uvavanyo lomatshini wazo zonke iintlobo zokutshintsha kwe-SF6, izixhobo ze-GIS ezidityanisiweyo, izitshixo ze-vacuum kunye nokutshintsha kweoli.
●Ubuchule obunamandla bokuchasana nokuphazamiseka.Inokuvavanywa ngokulula kwaye ilinganiswe ngokuchanekileyo kwisitishi esingaphantsi kwe-500KV.
●I-Accelerometer (ukhetho), inzwa yomgca, inzwa yokujikeleza, kulula ukuyifaka kwaye kulula.
●Yonke idatha yovavanyo lokutshintsha komatshini kunye nemephu ye-waveform ehambelana nayo ifunyenwe emva kokuba iswitshi yenziwe kanye.
●Gcina idatha yovavanyo lwentsimi kunye newotshi yexesha lokwenyani eyakhelweyo, elungele ukugcinwa kunye nokugcina umhla wovavanyo kunye nexesha.
●Ngesikrini se-LCD se-10.1inch, bonisa yonke idatha kunye nemephu, ngokukhanya okungasemva, ukulungiswa kwe-LCD kunye nokucima imemori.
●Ukusebenza kwemenyu enobubele, kulula ukuyisebenzisa.Ngeprinta eyakhelwe-ngaphakathi ukuprinta ngokukhawuleza zonke iziphumo zedatha.
●Ukuxhotyiswa nge-software yolawulo lokuhlalutya idatha, enokuthi iqhutywe kwi-intanethi nge-PC, kunye nefayile yefomethi yeWORD.Iziphumo zovavanyo zinokukhutshwa kuzo zonke iintlobo zeengxelo zovavanyo loshicilelo loshicilelo ukwenza uvavanyo lwasendle lube khompuyutha.
●Vula kwaye uvale ukhetho lwesantya kunye nomsebenzi ochazwe ngumsebenzisi ngokweemfuno, ulungele ukulinganisa isantya salo naluphi na uhlobo lokutshintsha.
●Ixesha:
Abafowunelwa abali-12 ngokwendalo abavulelekileyo (abavaliweyo).
Kwinqanaba longqamaniso
Ungqamaniso lwenqanaba ukuya kwisigaba
●Iyavala kwakhona:
CO, OC, ixesha leCOC,
Ixesha lokuqala lokuvula, ixesha lokuqala lokuvala, ixesha lesibini lokuvala, ixesha lokuvula, ixesha elifileyo, ixesha lokufa, akukho xesha langoku.
●Ukutsiba:
Vala ixesha lokutsiba, amaxesha, inkqubo kunye nefom yamaza yabafowunelwa ngamnye.
Ukuvula i-rebound amplitude yomfowunelwa ngamnye.
Isantya: isantya ekuqhagamshelwaneni sivula nje kwaye kuvalwe nje, isantya esiphezulu, ijika leempawu zokuhamba kwexesha.
Ukuhamba: uhambo lulonke, umgama ovulekileyo, uhambo olungaphezulu, uhambo oludlulayo, i-rebound amplitude.
Okwangoku: vula / vala okwangoku, umzobo we-waveform yangoku yekhoyili evulekileyo / evaliweyo.
I-voltage esebenzayo: eyakhelwe ngaphakathi DC0 ~ 300V / 20A yedijithali, umthombo wamandla ohlengahlengiswayo we-breaker, ugqibezela ngokuzenzekelayo uvavanyo lwesenzo se-LV se-breaker circuit kunye nokulinganisa ixabiso lombane wesenzo se-breaker circuit.
Ukuvala ukuchasana: ixesha lokuphoswa kwangaphambili, i-waveform yangaphambili kunye nexabiso lokumelana ne-resistor yokuvala ye-6 abafowunelwa.(ukhetho)
Uqhagamshelwano lwegraphite: ixesha elivulekileyo, lokuvala kunye ne-dynamic waveform ye-Siemens graphite contact switch kunye ne-3 okanye indlela ye-6 yoqhagamshelwano. (ukhetho)
Isiseko esipheliswe kabini: phantsi kwe-3 okanye i-6-indlela ye-double-port grounding, inokulinganisa ngokuchanekileyo ixesha lokuvula nokuvala.(ukhetho)
Ukumelana ne-Static: 1 * 100A umlinganiselo wokumelana noqhagamshelwano.
Ukuxhatshazwa okunamandla (i-Pre-insertion resistor): I-1 * 100A i-waveform yenguqu ye-wave of resistance ngexesha lesenzo se-breaker circuit.
●Usetyenziso Lwemeko-bume
Amandla oNgeniso: 220V±10%, 50Hz ± 10%, Uxinzelelo loMoya: 86-106kpa
Ubushushu: -10-40℃ Ukufuma: ≤80%RH
●Ukusebenza koKhuseleko
Ukumelana ne-Insulation>2MΩ
Amandla e-Dielectric: I-Shell inokumelana ne-voltage frequency voltage 1.5kV ngomzuzu we-1 ngaphandle kwe-flashover kunye ne-arcing.
●Iiparamitha ezisisiseko
Ixesha: Uluhlu 20000.0ms, isisombululo 0.01ms, impazamo 0.5%
Ukuvala ukuchasana: uluhlu lwe-10kΩ, min.isisombululo 1Ω, impazamo 0.5% (ukhetho)
Uqhagamshelwano lwegraphite: uluhlu lwe-200ms, min.isisombululo 0.1ms, impazamo 0.5% (ukhetho)
I-double-ends grounding: uluhlu lwe-200ms, min.isisombululo 0.1ms, impazamo 0.5% (ukhetho)
Ukuxhathisa okuzinzileyo: uluhlu lwe-1uΩ~10mΩ, min.isisombululo 0.01μΩ, impazamo 0.5%
Ukuxhathisa okunamandla: uluhlu lwe-10mΩ, min.isisombululo 1μΩ, impazamo 0.5%
Uvavanyo lwangoku: DC 50A, 100A (isigaba esi-3 silinganiswe ngexesha elinye)
Isantya: Uluhlu lwe-20.00m/s isisombululo 0.01m/s impazamo 0.5%
Uhambo:
| Iintlobo | Uluhlu | Isigqibo | Impazamo |
| Ivacuum breaker | 50.0mm | 0.1mm |
0.5% |
| SF6 umaphuli wesekethe | 300.0mm |
1mm | |
| I-oyileumephuli wojikelezo | 600.0mm |
Okwangoku: uluhlu 20.00A, isisombululo 0.01A
Amandla emveliso: DC 0-300V digital adjustable/20A (ukusebenza ngoko nangoko), isisombululo 1V.
Imilinganiselo: malunga ne-360mm (L)* 280mm (W)* 300mm (H)
Ubunzima: malunga ne-10kg
| Engundoqounit nge 10.1-intshi tablet | 1 iphec |
| I-accessory case | 1 pc |
| Itshaja yethebhulethi | 1 pc |
| Iadaptha esemgangathweni yaseMelika | iipcs ezi-2 |
| Rotary isivamvo sesantya | 1 pc |
| Uluvo lwesantya somgca50mm | 1 pc |
| Intambo yoqhagamshelo lomqondiso wesantya (5-ucingo olukhuselekileyo) | 1 pc |
| Ukuvula kunye nokuvala intambo yokulawula(3-core sheathed cable) | 1 pc |
| Ukuxhobisa kwangaphandleiyabhaqaintambo (ebomvu/emnyama, 2-core) | 1 pc |
| Intambo ephantsi | 1 pc |
| Qhagamshelana nentambo yovavanyo(4-core sheathed cable) | 1pc |
| CUvavanyo olululo lwentambo eyandisiweyo (5M, tyheli, luhlaza kwaye bomvu isiqwenga ngasinye, 3pcs emnyama) | 6iipcs |
| Intambo emfutshane (0.5m emnyama,2m mnyama) | iipcs ezi-2 |
| Ikhodi yamandla | 1 pc |
| Universal Joint kunye nesiseko umazibuthe | 1 iseti |
| Izixhobo ezikhethekileyo zokufakela ezisisigxina | Iseti e-1 |
| Iikliphu zovavanyo kunye neethimbles | 18 iipcs |
| Cintambo yovavanyo lokumelana ne-ontact(5M) | 1 pc |
| Iphepha lokuprinta | Imiqulu emi-2 |
| Intambo ye-USB | 1 pc |
| Isikhokelo somsebenzisi | 1 pc |
| Ingxelo yovavanyo lwasefektri | 1 pc |