I-GDKC-12A (GDKC-12B) (GDKC-13A) IsiHlalutyi seSaphuli seSekethe
I-high-voltage circuit breaker yenye yezona zixhobo zokulawula ezibalulekileyo kwinkqubo yamandla.I-GDKC-12A/B (GDKC-13A) isetyenziselwa ukuvavanya iimpawu eziguquguqukayo ze-high voltage breaker circuit.Kulula ukusebenza, ngokuchaneka okuphezulu.
●Ixesha: ixesha elivulekileyo / elivaliweyo, kwisigaba sokuvumelanisa, ukulungelelaniswa kwesigaba ukuya kwisigaba se-12contacts.
●Ukuvala i-resistor: ixesha lokutshintsha kwangaphambili, i-waveform yokutshintsha kwangaphambili kunye nokuchasana kwe-resistor yokuvala iziteshi ezi-6.
●Ukuvala kwakhona: vala-vula, vula-vala, vula-vala-ixesha elivulekileyo lomfowunelwa ngamnye.
●I-Bounce: ixesha lokutsiba lokuvala, amaxesha, inkqubo kunye nohlobo lwamaza lwabafowunelwa ngamnye.
●Isantya: isantya kuqhagamshelwano oluvulekileyo okanye oluvaliweyo, isantya esiphezulu, ijika leempawu zokuhamba ngexesha;eyokuqala ivuleke, eyokuqala ivale kwaye eyesibini ivuleke isantya sokuvala kwakhona.
●Ukuhamba: uhambo lulonke, uhambo oluvulekileyo, uhambo olungaphezulu, uhambo oludlulayo, i-bounce amplitude.
●Okwangoku: vula / vala okwangoku, umzobo we-waveform yangoku yekhoyili evulekileyo / evaliweyo.
●Umbane wokuSebenza: I-DC30 ~ 300V/20A yedijithali eyakhelwe-ngaphakathi, umthombo wamandla ohlengahlengiswayo webreaker, gqibezela ngokuzenzekelayo uvavanyo lwesenzo se-LV sesaphuli sesekethe kunye nokulinganisa ixabiso lentshukumo yombane wesaphuli sesekethe.
●IPC yomamkeli.
●Kufanelekile ukuvavanya iiparamitha zendlela yazo zonke iintlobo ze-SF6 i-circuit breaker, i-GIS yokudibanisa izixhobo zombane, i-vacuum circuit breaker, i-oil circuit breaker.
●Ubuchule obunamandla bokuchasana nokuphazamiseka.Ikwanakho nokuvavanya ngokulula kwaye ilinganise ngokuchanekileyo nokuba i-interbus iphila kwisikhululo esingama-500kV.
●Ngesivamvo sesantya sendalo yonke (ukhetho), isivamvo sesantya somgca, isivamvo sokujikeleza, kulula ukuyifaka.
●Isenzo sexesha elinye kuphela lokufumana yonke idatha kunye ne-wave wave ehambelanayo yovavanyo lwe-breaker mechanism.
●Idatha yovavanyo lokugcinwa kwamaqela angama-1000, iwashi yexesha langempela eyakhelwe-ngaphakathi, ekulungele ukugcina umhla kunye nexesha lovavanyo.
●Isibonisi sesikrini se-LCD, kunye nolungelelwaniso oluchaseneyo kunye nememori yokucima amandla.
●Umshicileli we-Buit-in, ukufumana yonke idatha kunye nomzobo nangaliphi na ixesha ngokukhawuleza.
●Nge-software yolawulo lohlalutyo lwedatha yesiphaluka.Inokunxibelelana nePC.Iziphumo zovavanyo zigcinwa ngokuthe ngqo kwi-hard disk, kwaye iyakwazi ukuvelisa kwiintlobo ezahlukeneyo zohlobo lwenaliti, i-laser okanye i-inkjet abashicileli beengxelo zovavanyo lokushicilela, ukwenza uvavanyo lwentsimi kwi-computer.
●Ukusebenzisa i-U disk ukugcina nokudlulisa idatha ngokuthe ngqo.
●Isoftware yokuhlalutya ehambelanayo ihlanganiswe ngokwenkcazo yokuvula, ukuvala isantya.Kufanelekile ukulinganisa isantya kuzo zonke iintlobo zokutshintsha.
●Usetyenziso Lwemeko-bume
Amandla oNgeniso: 220V±10%, 50Hz±10% / GDKC-12B: 230V±10%, 60Hz±10%
Uxinzelelo loMoya: 86-106kpa
Ubushushu: -10-40℃
Ukufuma: ≤80%RH
●Ukusebenza koKhuseleko
Ukumelana ne-Insulation>2MΩ
Amandla e-Dielectric: I-Shell inokumelana ne-voltage frequency voltage 1.5kV ngomzuzu we-1 ngaphandle kwe-flashover kunye ne-arcing.
●Iiparamitha ezisisiseko
a.Ixesha: Uluhlu lwe-20000.0ms isisombululo 0.01ms
Imposiso 0.1ms ±1dijithi phakathi kwama-2000ms
1ms±1dijithi phakathi kwama-20000ms
I-GDKC-12B Iiparamitha ezisisiseko
a.Ixesha: Uluhlu lwe-20000.0ms isisombululo 0.01ms
Imposiso 0.01ms ± 2digit phakathi kwama-250ms
0.1ms ± 2digit phakathi kwama-2500ms
1ms±2 idijithi phakathi kwama-20000ms
I-GDKC-13A Umhlalutyi weSekethe yeSaphuliIiparamitha ezisisiseko
Ixesha: Uluhlu 4000.0 + 6000.0 ms isisombululo 0.1ms
Imposiso 0.1ms ± idijithi enye ngaphakathi kwe-100ms
0.1% ± idijithi enye ngaphezulu kwe-100ms
Ixesha elifanayo
b.Isantya: Uluhlu lwe-20.00m/s isisombululo 0.01m/s
Imposiso ±0.1m/s±1dijithi phakathi kwe-0-2m/s
±0.2m/s±1dijithi ngaphezulu kwe-2m/s (± 0.2m / s ± idijithi enye ngaphezu kwe-100ms)
c.Uhambo:
Iintlobo | Uluhlu | Isigqibo | Impazamo |
Ivacuum breaker | 50.0mm | 0.1mm | 0.1±1idijithi |
SF6 umaphuli wesekethe | 300.0mm | 1mm | |
I-oyileumephuli wojikelezo | 600.0mm |
d.Okwangoku: uluhlu lwe-20.00A isisombululo 0.01A
e.Amandla emveliso: DC0-300V digital adjustable / 20A (ukusebenza ngoko nangoko), isisombululo 1V.
f.Imilinganiselo: 360mm (L)* 280mm (W)* 300mm (H)
g.Ubunzima: 10kg (9kg)
h.GDKC-13A Ubunzima: 9kg