I-GD-2136H yeNkqubo yokuLawulwa kweFault Cable
Inkqubo yeFault yeCable ye-GD2136H sisixhobo esibalulekileyo sokugcina zonke iintlobo zeentambo.Isebenzisa iindlela ezahlukeneyo zokubona ukuvavanya iimpazamo zentambo, ezifanelekileyo kumanqanaba ahlukeneyo iintambo zamandla ombane kunye neentambo zonxibelelwano.
Inkqubo iqulathe ngezantsi iiyunithi:
1. GD-2131H Impulse Generator
2. GD-2132 iCable Fault Locator
3. GD-2133 Cable Fault Tester
4. Ezinye izincedisi
I-GD-2131H Impulse Generator

Isetyenziselwa ukuvelisa i-HV impulse xa usebenzisa indlela ye-impulse flashover ukukhangela impazamo ephezulu yokuphazamiseka.
●Ikhono elivuthayo elinamandla, amandla okushisa aphezulu yi-1000W, indawo yokuphuka ingatshiswa ngexesha elifutshane kwaye ukuchasana kwendawo yokuphuka kuyancipha.
●Ukuba usebenza kunye ne-GD-2133 Cable Fault Tester, zimbini iindlela zokufumana indawo:
a.I-voltage ephantsi ye-pulse: Ukuba usebenzisa i-GD-2133 kuphela, isiphaluka esivulekileyo kunye neziphene ezisezantsi zokumisa intambo zinokufumaneka, kwaye ubude bentambo bunokulinganiswa okanye isantya samaza sentambo sinokubonwa.
b.I-flashover yamandla ombane aphezulu: Ukukhupha i-pulse yamandla ombane kwindawo enempazamo ithathwa njengesampulu ngokukhupha umsantsa wesphere, onokuthi ufumane umgama wempazamo.
●Yenza impembelelo yefrikhwensi esisigxina.Ukuba usebenza kunye ne-GD-2132 Cable Fault Locator, kukho imisebenzi elandelayo:
a.Indlela yomsindo isetyenziselwa ukugqibezela indawo echanekileyo yendawo yokuchasa ngokubanzi kunye neempazamo ze-flashover.
b.Ukukhomba indlela yentambo, chonga intambo ekhethekileyo.
c.Ukophuka kwesinyithi (isiseko esifileyo), kusetyenziswa umlinganiso wemagnethi ukuze ufumane indawo ngokuchanekileyo.
●Inokusetyenziswa kwakhona kwi-DC HV yokumelana novavanyo.
●Ubonelelo lwamandla okufakwayo: AC 220V,50Hz
●Umbane ophumayo: DC 0-32kV (enokulungiswa)
●Amandla alinganisiweyo: 2000VA
●Max.energy: 2048J, 4uF
●Umbane we-flashover ye-DC: 32kV
●I-DC flashover yangoku: 63mA
●I-Max.impulse yangoku: 500mA
●Indlela yokukhupha: I-DC HV, ixesha elinye, umjikelo
●Ixesha lokukhupha umjikelo: 3-6 imizuzwana
●Ubushushu bokusingqongileyo:0-40℃
●Ukufuma:<75% RH
●Ukuphakama: <1000m
●Inqanaba lokugquma: A
●Ubungakanani: 430 * 540 * 410mm
●Ubunzima: malunga ne-31kg.

Kubandakanya isidluliseli, umamkeli, i-Inductive probe, ukubhaqwa kohlobo olunokubakhoisakhelo.Kufanelekile ukuvavanya zonke iintlobo zentambo yamandla kunye ne-metallic conductor.
Umsebenzi wayo oyintloko kukufumana indawo engafanelekanga yokugquma, ukufumanisa isiphaluka kunyeubunzulu bentambo yamandla.
●Uvakalelo oluphezulu
●Ukukhukuliseka okusezantsi
●Ukuchaneka okuphezulu kwendawo
●Ukuchasana nokuphazamiseka
●Isikrini se-LCD ukubonisa isignali kunye nesimo
●I-Li-ibhetri eyakhelwe-ngaphakathi etshajekayo
●Ukulandela kunye nokubeka umgama: intambo yendawo 3km, enye intambo ukuya kwi-20km
●Ukufumana uluhlu lwe-impedance: 0-5MΩ.
●Ukuchaneka kwendawo: ≤±10cm.
●Ubunzulu bekhebula lokubona: <3m.

Inokuvavanya iimpazamo ze-high-impedance flashover, ephezulu-phantsiukumelana nomhlaba, i-short-circuit, ukuqhawula intambo, uxhulumaniso olubikuzo zonke iintlobo zeentambo zamandla (iqondo le-voltage 1kV-35kV),intambo yendawo, intambo yonxibelelwano, i-coaxial-cable kunye nomgca wentsimbi.
Kananjalo inokulinganisa ubude bekhebula kunye nesantya sokusasaza sesantya sombane kwintambo.
●Uvavanyo olukhuselekileyo, olukhawulezayo noluchanekileyo.Isebenzisa indlela ye-LV impulse kunye nokufunyanwa kwe-HV flashover, evavanya zonke iintlobo zeempazamo zentambo.Ngokukodwa kwi-flashover kunye neempazamo eziphezulu ze-impendance zeentambo, zinokuvavanywa ngokuthe ngqo ngaphandle kokutshisa;ukuba ixhotyiswe nge-acoustic measurement locator, indawo echanekileyo yephutha inokuqinisekiswa ngokuchanekileyo.
●Ukusebenzisa iteknoloji yesampula yedatha yesantya esiphezulu.Isantya sesampula se-A / D yi-100Mhz, ukwenza isisombululo sokufunda kwesixhobo si-1m kwaye indawo engaboniyo yokubona yi-1m.
●Ifom ye-Wave kunye nedatha iboniswa ngokuzenzekelayo kwisikrini esikhulu se-LCD.
●Ifom yamaza kunye nokugcinwa kweparameter, khumbula umsebenzi.
●Umsebenzi wokuthelekisa uvavanyo lwe-waveform yempazamo yentambo kunye ne-wave wave eqhelekileyo.
●Ifom ye-Wave yokwandisa umsebenzi.
●Bonisa ngokuthe ngqo indawo yempazamo kunye nendawo yokuvavanya umgama othe ngqo okanye umgama ozalanayo.
●Guqula isantya sokusasazwa nangaliphi na ixesha ngokweentambo zovavanyo ezahlukeneyo.
●Ibhetri eyakhelwe-ngaphakathi egcwalisekayo.Ubungakanani obuncinci, obuphathekayo ukuthwala.
●Umgama wokuvavanya obuninzi: 15km(Ucingo oluvulekileyo ukuya kuthi ga kwi-100km).
●Ukubona ubumfama: 1m
●Isigqibo: 1m
●Ukusetyenziswa kwamandla: 5VA
●Ubushushu bendalo: 0-40℃(umlinganiselo wobushushu:-10℃-50℃)
●Ukufuma okunxulumeneyo: 40℃(20~90) %RH
●Uxinzelelo lwe-Atmospheric: 86-106Kpa
●Ubungakanani: 275 * 220 * 160mm
●Ubunzima: 1.8kg

Ezinye izincedisi ziquka i-AF Stethoscope, i-Headphones, i-Grounding Pin, i-PD Locating Rack, i-RF Tracking Rod.