I-Power transformer winding deformation tester (indlela yokuphendula ngokuphindaphindiweyo) isekelwe kumlinganiselo wemilinganiselo yeempawu ze-transformer yangaphakathi, ithatha i-internal fault frequency analysis analysis (FRA), inokugweba ngokuchanekileyo iimpazamo zangaphakathi ze-transformers.
Emva kokugqitywa koyilo kunye nokuveliswa kweenguqu, iikhoyili kunye nesakhiwo sangaphakathi sigqitywe, ngoko ke i-coil ye-multi-winding transformer, ukuba inqanaba le-voltage kunye nendlela yokuphefumula iyafana, iiparamitha ezihambelanayo (Ci, Li) nganye. ikhoyili iya kumiselwa.Ke ngoko, ukuphendulwa kweempawu zokuphindaphinda kwekhoyili nganye nako kuya kumiselwa, ngoko ke iifrikhwensi zeekhoyili ezihambelanayo zezigaba ezithathu ziyathelekiseka.
Ngexesha lovavanyo lwe-transformer, kwimeko ye-inter-turn, i-inter-phase short circuit, okanye i-coil displacement ebangelwa kukungqubana ngexesha lothutho, kunye nokuguqulwa kwekhoyili okubangelwa kuxinzelelo lwe-electromagnetic ngexesha lokusebenza phantsi kweemeko ezimfutshane kunye neempazamo, iiparamitha zokusabalalisa. ye-transformer windings iya kutshintsha, nto leyo echaphazela kwaye itshintshe iimpawu ze-domain ye-frequency ye-transformer yokuqala, ezizezi utshintsho lwempendulo yefrikhwensi kubukhulu kunye nokutshintsha kwamanqaku amaza.Umvavanyi we-transformer winding ophuhliswe ngokwendlela yokuhlalutya impendulo yinoveli yesixhobo se-NDT sokubona impazamo yangaphakathi ye-transformer.Isebenza ekubhaqweni kwempazamo yesakhiwo sangaphakathi kwiziguquli zamandla ezingama-63kV-500kV.
Umvavanyi woguqulo loguqulo lokujija kukumisela iqondo lotshintsho kwi-windings yangaphakathi ye-transformer esekelwe kubuninzi benguqu, ubukhulu kunye nommandla ochaphazela utshintsho kunye nokuthambekela kwenguqu yempendulo ye-frequency ebalwa ukusuka kwiinguqu zempendulo kwimimandla eyahlukeneyo yamafrikhwensi yokuguquka kwangaphakathi kwe-transformer. iparameters, kwaye ke inokunceda ukufumanisa ukuba i-transformer yonakaliswe kakhulu, okanye idinga ukulungiswa okukhulu ngokuhambelana neziphumo zokulinganisa.
Kwi-transformer esebenzayo, kungakhathaliseki ukuba umzobo we-domain ye-frequency character igcinwa, ngokuthelekisa ulwahlulo phakathi kwe-inter-coil character spectra ye-faulted transformer, inokugqiba ubungakanani bokusilela ngokunjalo.Ngokuqinisekileyo, ukuba ulondoloze i-original transformer windings feature drawings, kuya kuba lula ukubonelela ngesiseko esichanekileyo seemeko zokusebenza, uhlalutyo lwe-post-fault kunye nokulungiswa kokugcinwa kwe-transformer.
Umvavanyi wokuguqula i-deformation ye-Transformer iqulunqwe yikhompyutheni yekhompyutheni kunye nomlawuli omncinci owenza inkqubo yokulinganisa echanekileyo kunye nesakhiwo esihlangeneyo, ukusebenza okulula, kunye nomsebenzi wohlalutyo olupheleleyo olupheleleyo, olunokuthi luqhutywe ngokubhekisele kwincwadana yemiyalelo okanye ngoqeqesho lwexesha elifutshane.
●Ukufumana kunye nokulawula usebenzisa i-high-speed, i-microprocessor edibeneyo kakhulu.
●Unxibelelwano lwe-USB interface esetyenziswa phakathi kwelaptop kunye nesixhobo.
●I-Wireless WIFI interface okanye iBluetooth (ukhetho) esetyenziswa phakathi kwekhompyutha yelaptop kunye nesixhobo.
●I-Hardware yamkela itekhnoloji ezinikeleyo ye-DDS yedijithali yesantya esiphezulu sokuskena (i-USA), enokuthi ichaze ngokuchanekileyo iziphene ezinje ngokujija okugqwethiweyo, ukugobhoza, ukuguquka, ukuthambeka, ukujika phakathi kweesekethe ezimfutshane kunye nesigaba esifutshane soqhagamshelwano.
●Isantya esiphezulu se-double-channel 16-bit A/D isampuli (kuvavanyo lwasendle, hambisa itephu itshintshi, kunye nejiko lamaza libonisa utshintsho olucacileyo).
●Ubungakanani bemveliso yesignali buhlengahlengiswa yisoftware, kwaye ixabiso lencopho le-amplitude yi-± 10V.
●Ikhompyutha iya kuhlalutya iziphumo zovavanyo ngokuzenzekelayo ize ivelise amaxwebhu ekhompyutha (iWord).
●Isixhobo sinezinto ezimbini zokulinganisa: umlinganiselo wokuskena rhoqo kunye necandelo lokulinganisa ukuskena amaza, iyahambelana nemowudi yokulinganisa yamaqela amabini obugcisa eTshayina.
●Iimpawu ze-amplitude-frequency zihambelana neenkcukacha zobugcisa besizwe kwi-amplitude-frequency features tester.Ulungelelwaniso lwe-X (i-frequency) lunesalathisi somgca kunye nesalathiso se-logarithmic, ngoko ke umsebenzisi unokushicilela ijika ngesalathiso somgca kunye nesalathiso se-logarithmic.Umsebenzisi unokukhetha nokuba ngokweemfuno zangempela.
●Inkqubo yohlalutyo lwedatha yovavanyo oluzenzekelayo,
Uthelekiso oluthe tyaba lokufana okujikelezayo phakathi kwezigaba ezithathu A, B kunye no-C
Iziphumo zezi zilandelayo:
●Ukuhambelana okugqwesileyo
●Ukuhambelana kakuhle
●Ukungaguquguquki kakubi
●Ukungaguquguquki okubi
Ukuthelekisa ixesha elide iAA, BB, CC ibiza idatha yoqobo kunye nedatha yangoku kwisigaba esifanayo sokuthelekisa i-deformation yomoya.
Iziphumo zohlalutyo zezi:
●Ukujija okuqhelekileyo
●I-deformation ephakathi
●Utshintsho oluphakathi
●I-deformation enzima
Uxwebhu lwe-elektroniki lwe-Word lunokwenziwa ngokuzenzekelayo ukuze lugcinwe kwaye luprintwe.
Isixhobo sinokuhlangabezana ngokupheleleyo neemfuno zobugcisa bomgangatho wombane we-DL/T911-2004 "Uhlalutyo lokuphendula ngokuphindaphindiweyo kwi-deformation ejikelezayo yeenguqu zamandla".
Imowudi yokuskena:
1. Unikezelo lokuskena ngomgca
Uluhlu lokulinganisa ukuskena: (10Hz) -(10MHz) 40000 indawo yokuskena, isisombululo 0.25kHz, 0.5kHz kunye ne-1kHz.
2. Isegment frequency scanning measurement distribution
Uluhlu lokulinganisa ukuskena rhoqo: (0.5kHz) - (1MHz), iindawo zokuskena ze-2000;(0.5kHz) - (10kHz);(10kHz) - (100kHz);(100kHz) - (500kHz);(500kHz) - (1000kHz)
Ezinye iiparamitha zobugcisa:
1. Uluhlu lomlinganiselo we-Amplitude: (-120dB) ukuya (+20 dB);
2. Ukuchaneka komlinganiselo we-Amplitude: 1dB;
3. Ukuskena ukuchaneka kwamaza: 0.005% / 0.01%;
4. Ukuphazamiseka kwegalelo lomqondiso: 1MΩ;
5. Ukuphazamiseka kwemveliso yomqondiso: 50Ω;
6. Ubungakanani bemveliso yesignali: ± 20V;
7. Inqanaba lokuphinda uvavanyo lwenqanaba: 99.9%;
8. Imilinganiselo yezixhobo zokulinganisa (LxWxH): 350*300*140 (mm) / 300*340*120 (mm);
9. Ubungakanani bebhokisi ye-aluminium yesixhobo (LxWxH): 390*310*340 (mm) / 310*400*330 (mm);
10. Ubunzima bubonke: 13kg / 10kg;
11. ubushushu bokusebenza: -10℃~+40℃;
Ubushushu bokugcina: -20℃~+70℃;
Ukufuma okuhambelanayo: <90%, Ukungaguquguquki;
| Iyunithi ephambili | 1 |
| Ukukhokelela kuvavanyo lokuphendula rhoqo 50W/(>15m) | 2 |
| Ibamba lovavanyo, tyheli, luhlaza(200A) | 2 |
| Intambo yomhlaba (emnyama, 5M ucingo lobhedu) | 4 |
| Ibamba lokugalela phantsi(elimnyama) | 2 |
| Intambo yonxibelelwano ye-USB | 1 |
| Ufakelo lweSoftware yeCD-ROM ifomathi yeVCD | 1 |
| Ufakelo lweSoftware ye-USB disk 16G | 1 |
| I-Fuse 0.5A | 3 |
| Intambo yamandla kunye neadaptha | 1 |
| Isikhokelo somsebenzisi | 1 |
| Ikhadi lewaranti | 1 |
| Uluhlu lokupakisha | 1 |
| Ingxelo yovavanyo lwasefektri | 1 |