Ngo-Agasti, iichwephesha zokuthengisa emva kwe-HV Hipot zaya e-Xiangyang.Injongo yolu hambo ibikukubonelela ngeenkonzo zokulungiswa kwamandla ombane kwi-Xiangyang Power Supply Company.
Emva kokufika kwindawo, ngoncedo kunye nentsebenziswano yomthengi, ukufakwa kwe-generator ye-voltage impulse voltage kuya kwenziwa.
Ukulungiswa kwendawo ye-GDCY-400kV umbane we-impulse voltage generator
Ulungelelwaniso lomgama webhola ekwisiza: ulungelelwaniso lomgama webhola yomzimba kunye nokulinganisa umgama webhola ye-chopper (3000/200/umlinganiselo)
Uvavanyo oluqhutywayo kwindawo: 30KV iimvavanyo ezininzi ezivumayo nezingalunganga (ukudibana ne-T1=1.2±30%/T2=50±20%us/TC=2 ukuya kwi-6us)
Uvavanyo lwamandla kwisiza: i-voltage elinganiselweyo ye-80% yokuphuma
Uqeqesho lwethiyori kunye nokusebenza kwindawo:
Ukuziqhelanisa nomthengi-uvavanyo olufanisiweyo lwemveliso yovavanyo: i-10KV isiguquli samandla
1. Uvavanyo lwamaza ngokupheleleyo
Iimfuno zovavanyo: umbane wovavanyo 75KV, ixesha le-waveform T1=1.2±30%/T2=50±20%us
Ukusebenza kwintsimi: usebenzisa i-voltage yemigangatho emibini
Ukumodareyitha kwamaza kwindawo:
Ukuxhathisa intloko yamaza: 150Ω kwinqanaba lokuqala, 500Ω kwinqanaba lesibini (2 1KΩ ngokuhambelana)
Ukumelana nomsila wamaza: isigaba sokuqala se-45Ω, isigaba se-2nd 45Ω
Uvavanyo lomsebenzi kunye nefomu yamaza:
2. Uvavanyo lokuvala
Iimfuno zovavanyo: amandla ombane wovavanyo 85KV, ixesha lentloko yamaza T1=1.2±30%, ixesha elisikiweyo TC=2 ukuya kwi-6us
Ukusebenza kwintsimi: usebenzisa i-voltage yemigangatho emibini
Ukumodareyitha kwamaza kwindawo:
Ukumelana nentloko yamaza: iNqanaba 1 75Ω, iNqanaba 2 500Ω (2 1KΩ ngokuhambelana)
Ukumelana nomsila wamaza: isigaba sokuqala se-45Ω, isigaba se-2nd 45Ω
Uvavanyo lomsebenzi kunye nefomu yamaza:
Emva kolu chungechunge loqeqesho, umthengi unokuqonda okunzulu kweseti yonke yezixhobo, okwenza umthengi aqiniseke ngakumbi ekusebenzeni kwangempela!
Ixesha lokuposa: Aug-24-2022