I-GDSF-411CPD SF6 I-Gas Comprehensive Analyzer
I-GDSF-411CPD SF6i-gas comprehensive analyzer sisixhobo esiphathwayo esenzelwe ukulinganisa iSF6indawo yombethe wegesi, ubunyulu kunye nemveliso yokubola.Inxalenye engundoqo kunye nendlela yesipili esibandayo isetyenziselwa ukuvavanya indawo yombethe, inzwa yaseYurophu kunye nendlela yokuvavanya i-SF.6ukucoceka kwegesi kunye nenzwa ye-electrochemical evela kwiMembrapor ukuvavanya i-SF6imveliso yokubola kwegesi.Ngaphandle koko, sikwathatha iitshiphusi zehardware yobuchwephesha kunye ne-algorithms yesoftware egqwesileyo ye-STMicroelectronics.
SF6Ukufuma
Indlela yokulinganisa | Indlela yesipili esipholileyo (I-Stirling Refrigeration) |
Uluhlu lomlinganiselo | Indawo yombethe -100℃--+20℃(ama-90s kumlinganiselo wenqaku elinye), imposiso: ngcono kune ±0.2℃ |
Ukuphinda-ubuchule | ± 0.1 ℃ |
Isigqibo | 0.01℃ |
Iyunithi yokubonisa | ℃, ppm, ℃ P20(ixabiso eliguquliweyo kuma-20℃) |
SF6Ubunyulu
Indlela yokulinganisa | UmGaqo woMlinganiselo we-Infrared (NDIR series sensors) |
Uluhlu lokulinganisa | 0 ~ 100% SF6, imposiso: ingcono kune ± 0.3%FS |
Ixesha lokuphendula | [90%] 60s |
Ukuphindaphinda | ± 0.3% |
Isigqibo | 0.01% |
Iyunithi yokubonisa | % |
SF6Iimveliso zokubola
Indlela yokulinganisa | UmGaqo woMlinganiselo we-Electrochemical (i-Electrochemical series sensors from Membrapor) |
Uluhlu lomlinganiselo | SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0 ~ 50ppmv |
Ukuchaneka | SO2: 10ppmv ±3% H2S: 10ppmv ±3% CO: 50ppmv ±4% HF: 10ppmv ±3% |
Ukuphinda-ubuchule | SO2: 10ppmv ±2% H2S: 10ppmv ±2% CO: 50ppmv ±2% HF: 10ppmv ±2% |
Isigqibo | 0.01ppmv |
Iyunithi yokubonisa | ppmv |
Iiparamitha ngokubanzi
Ukunikezwa Amandla | I-220VAC ± 10%, i-50Hz, ukusetyenziswa kwe-AC / DC, ukusebenza okuqhubekayo kungaphezu kweeyure ze-8. |
Sebenzisa ubushushu bokusingqongileyo | -20--+60℃ |
Ukufuma kokusingqongileyo | 90%RH |
Impembelelo yexabiso lomlinganiselo | Akukho mpembelelo yoxinzelelo kunye nokuhamba |
Ubungakanani | 570*420*280mm |
Ubunzima | Akukho ngaphezu kwe-20kg. |
UMvavanyi ongundoqo | Iqhekeza eli-1 |
Iadaptha | Iseti e-1 |
Umbhobho weTeflon (ubandakanya ivalve yohlengahlengiso kunye nesinxibelelanisi esikhawulezayo) | Iseti e-1 |
Umbhobho womsila | Iseti e-1 |
Iphathi ezisecaleni | Iseti e-1 |
Itshaja | Iqhekeza eli-1 |
Isikhokelo somsebenzisi | Iqhekeza eli-1 |
Ingxelo yoVavanyo | Iqhekeza eli-1 |