GDJB-6000D Smart Substation Relay Protection Test System
I-GDJB-6000D ixhotyiswe nge-amplifier yamandla ephezulu kwaye isekelwe kwiqonga elinamandla le-PowerPC+X86.Yamkela uyilo lwemodyuli kwaye inemisebenzi enamandla, ukuchaneka okuphezulu, ubungakanani obuncinci kunye neempawu zobunzima obulula.Iyakwazi ukuvavanya umsebenzi kunye nokusebenza kweyunithi yokudibanisa, isixhobo sokukhusela i-relay, umlinganiselo kunye nesixhobo sokulawula, iitheminali ezihlakaniphileyo njl. Zilungele kakhulu izityalo zamandla, izitishi, iiyunithi ezahlukeneyo zophando lwezenzululwazi kunye namashishini okuvelisa izixhobo.
●Smart Test Modyuli
Ukuhlela itemplate yovavanyo olukrelekrele kuyaxhaswa.Izinto zovavanyo zinokudibaniswa ngokungenamkhethe ngexesha lenkqubo yovavanyo kwaye zigcinwe njengeefayile zeprojekthi zokuvavanya kwakhona ukuphucula ukusebenza kovavanyo kwinqanaba lokugqibela lokuhlola nokuphelisa.
●Uvavanyo oluzenzekelayo
Ngokukhuselwa kwendawo kunye nokukhusela idijithali umsebenzi wokuvavanya ngokuzenzekelayo, zonke izinto zokuvavanya zesixhobo esisodwa sokukhusela zingagqitywa ngesitshixo esinye.
●Iimowudi zokuskena ezininzi
Ixhasa i-amplitude, isigaba, i-frequency, i-impedance, i-vector, ulandelelwano, kunye namandla enziwa ngovavanyo lwemanyuwali okanye oluzenzekelayo, lukwaxhasa uvavanyo lokutshintsha oluzenzekelayo ngokwendlela yokuhlelwa, ukutyibilika kunye nokudibanisa.
●Umboniso womzobo weterminal ebonakalayo
Inkxaso ye-terminal ye-terminal ebonisa umsebenzi wokubonisa umzobo, ukuhamba kwedatha kucacile.
●Thumela kwaye ufumane imiyalezo ngexesha elinye
Inkxaso ye-IEC61850-9-1, i-IEC61850-9-2 kunye ne-GOOSE imveliso yomyalezo wedijithali obonakalayo.Isignali yeGOOSE inokuthunyelwa kwaye ifunyenwe ngokuzimeleyo, kwaye inokuthumela kwaye ifumane nge-interface ye-Ethernet ye-optical kunye ne-IEC 61850-9-2.
●FT3/Eyandisiweyo FT3
Inkxaso ye-FT3, i-FT3 yokwandisa kunye ne-DL / T 282 imveliso yomyalezo, kunye nenkxaso ye-2M / 4M / 6M / 8M / 10M izinga le-baud ye-UART encoding kunye ne-5M / 10M / 20M ye-encoding yaseManchester.
●Uvavanyo olungaqhelekanga
Ngomsebenzi ongaqhelekanga womyalezo we-analog, unokulinganisa ukungaqhelekanga kumgangatho, ukuthumela i-jitter frequency, ukulibaziseka okungaqhelekanga, ukulahleka kwepakethi, ngaphandle kwenyathelo, ukutsiba kwenombolo ye-serial, imowudi yokugcinwa, utshintsho lwenyani kunye nolunye uvavanyo.
●Impazamo yokudlala
Ixhasa ukulinganisa impazamo kunye nomsebenzi wokudlala idatha ye-COMTRADE.
●Inkonzo ye-MMS
Ngomsebenzi wokufunda nokubhala weMMS, unokufunda nokubhala useto olukrelekrele lwezixhobo ze-IED kunye nolunye ulwazi loqwalaselo.
●Ungqamaniso lwexesha kunye nokunika ixesha
Ngomsebenzi we-synchronous trigger, inkxaso yokufikelela ngokuthe ngqo kwi-antenna ye-GPS / BD ye-antenna yexesha, iphinde ixhase i-IRIG-B, i-PPS kunye ne-PTP 1588 imodi yexesha kwaye inokuxhasa ukuphuma kwangaphandle kwe-IRIG-B, i-PPS kunye ne-PTP 1588 ixesha lokunika uphawu.
●Uqhagamshelwano olunzima lwegalelo lokubini kunye nemveliso yokubini
Ubuninzi begalelo busebenza kunye nabafowunelwa abaguquguqukayo, kunye nohlobo lwegalelo kunye ne-voltage yegalelo zibonwa ngokuzenzekelayo.Amatshaneli ahlukanisiwe komnye nomnye, kunye ne-polarity reverse uxhumano kunye ne-alarm prompt.
●Ukufumana umyalezo kunye nohlalutyo
Ngomyalezo ofumana kunye nomsebenzi wokuhlalutya, umyalezo ofunyenweyo unokuvulwa kunye ne-ZHNPA yokuhlalutya okanye ukuthumela ngaphandle.
●Imowudi yefiber enye
I-optical port isekela ukuhanjiswa kwefayibha enye kunye nokwamkelwa kwefayibha enye kwaye ixhasa uvavanyo lwamandla okukhanya.
●Isignali encinci ye-analog
Ixhotyiswe nge-analog encinci ye-interface ye-analog, ixhasa i-12 indlela ye-analog encinci ye-input, inokulinganisa -7V ~ 7V i-voltage ye-AC, ixhasa i-12 indlela ye-analog yemveliso encinci ye-analog, kwaye inokuvelisa -7V ~ 7V i-AC voltage.
●Ukusebenza ngokuchukumisa
Ixhotyiswe nge-10.4 intshi ye-high-resolution display exhasa ukusebenza kwe-touch.
●Uqhagamshelo olungenazingcingo
Nikeza umsebenzi wovavanyo olukude, kunye nemodyuli yeWiFi, esebenziseka lula.
IEC 61850 izibuko lonxibelelwano | |
Umsebenzi | Naluphi na ulungelelwaniso lwe-IEC 61850 9-1/9-2 SMV transmission, ukufumana okanye iGOOSE transmission kunye nolwamkelo |
Uhlobo lwesinxibelelanisi | Izibuko le-LC elibonakalayo |
Ubungakanani | 8 izibini, 6 ngababini * 100M adaptive, 2 ngababini * 100/1000M adaptive |
Ubude wamaza | 1310nm |
IEC 60044 izibuko lonxibelelwano | |
Umsebenzi | GB/T 20840.8, DL/T 282, Q/GDW441 umyalezo ofumana kunye nokuthumela |
Uhlobo lwesinxibelelanisi | ST |
Ubungakanani | I-6 * ukuthumela i-interface, i-2 * i-interface yokufumana |
Isigaba | |
Uluhlu | 0~360° |
Ukuchaneka | ±0.1° |
Isigqibo | 0.1° |
Ukuphindaphinda | |
Uluhlu | 0 ~ 1000Hz |
Ukuchaneka | <±0.001Hz(0~65Hz) <±0.01Hz(65~450Hz) <±0.02Hz(450~1000Hz) |
Isigqibo | 0.001Hz |
Ixesha | |
Uluhlu | 10ms ~9999.999s |
Isigqibo | 1ms |
Igalelo lomfowunelwa kabini | |
Ubungakanani | Izibini ezi-8, zinokudityaniswaunxibelelwano olungasebenziyo kunye noqhagamshelwano olunokwenzeka (0~250V) |
Isiphumo soqhagamshelwano lweBhinary | |
Ubungakanani | Izibini ezi-6, izibini ezi-2 ziphuma ngokukhawuleza |
Ukuqhawula umthamo | I-DC250V /0.5A |
Ixesha lokuphendula | <100us |
Ngqamanisa | |
Uhlobo lwesinxibelelanisi | GPS/BD ANT;I-IRIG-B/PPS isignali yokubona;I-IRIG-B / PPS isignali yombane;IEEE 1588 |
Ubungakanani | I-1 * GPS / BD ANT; I-2 * IRIG-B / PPS isignali ye-optical : 1 * ukuvumelanisa ixesha, i-1 * ixesha lokunikela; Izibini ezi-2 * I-IRIG-B / PPS isignali yombane : izibini ezi-1 * ulungelelwaniso lwexesha, izibini ezi-1 * ukunika ixesha; Izibini ezi-1* IEEE 1588 |
Uqhagamshelo olungenazingcingo | |
Uhlobo lwesinxibelelanisi | I-WIFI |
Uqhagamshelwano ngeentambo | |
Uhlobo lwesinxibelelanisi | 100M Lan port , RJ45 |
Ubungakanani | Iziqwenga ezi-2 |
Igalelo lesiginali ye-analog encinci | |
Uhlobo lwesinxibelelanisi | Iplagi yeAviation, amandla ombane e-AC |
Ubungakanani | 12 itshaneli |
Imveliso ye-analog encinci | |
Uhlobo lwesinxibelelanisi | Iplagi yeAviation, amandla ombane e-AC |
Ubungakanani | 12 itshaneli |
Ukunikezwa Amandla | |
I-Voltage | AC/DC 220V , Ukutenxa okuvumelekileyo: -20% ~ 15% |
Ukuphindaphinda | 47 ~ 65Hz |
Ujongano lwe-USB | |
Ubungakanani | Iziqwenga ezi-2 |
Indawo yokusebenza | |
Ubushushu bokusebenza | -10℃~50℃ |
Ukufuma | ≤95%,ukungaguquguquki |
Abanye | |
Ubunzima | 5.5 kg |
Ubungakanani | 146×390×212mm(L×W×H) |
Ujongano lwe-Intanethi | RJ45 |
Bonisa | 10.4 intshi umbala wokwenyani LCD touch screen |